                   MICROPROCESSOR TRMS MAXIMUM DEMAND CONTROLLER

                          MODEL - 8100 B MICROPROCESSOR TRMS MAXIMUM DEMAND CONTROLLER


    UNIQUE FEATURES

* Displays 12 parameters simultaneously
3V, 3A, W, Var, WH, VarH, PF, Hz, (12 parameters)
* Applicable Standard
DIN-IEC 688
* Suitable For
1Φ2W, 1Φ3W, 3Φ3W, 3Φ4W systems.
* 10 Years Power-Off Memory for set data
* With Rs485 Modbus Output
* User friendly setting of Demand parameters
* Demand Time interval setting (0-60 minutes)
* Synchronising time with Electricity Board meter timing.
* Maximum Demand (Sanctioned Demand) & Target Demand Setting.
* Displays Demand forecast
* Displays Remaining Time interval (of the demand period).
* Displays Present Demand.
* Displays usable remaing Demand.
* Software for Load & Demand Analysis (optional).
OUTPUT :

4 Relay outputs for Demand Control : In this instrument we can set the TARGET DEMAND (approx. 10%) below the SANCTIONED Demand. When the present Demand exceeds the target demand, the relay output switches ON. These relay outputs can be connected to least priority loads. When the relay turns on, the loads are switched off. When the present demand falls below the target demand, the relays switches ON the loads one by one. Delay time can be set for the relay control. Thus the present demand never exceeds the sanctioned demand & the customer is saved from paying penalty.

This instrument displays the remaining usable Demand, so that the load schedule can be programmed accordingly.

DEMAND MANAGEMENT & DEMAND CONTROL :
The MAXIMUM DEMAND CONTROLLER indicates MAXIMUM DEMAND (SANCTIONED), TARGET DEMAND, PRESENT DEMAND, DEMAND FORECAST & REMAINING USEABLE DEMAND & REMAINING TIME DURING ONE CYCLE. THESE FEATURES ARE MOST ESSENTIAL FOR PROPER DEMAND MANAGEMENT.

MAXIMUM DEMAND : It is the Maximum Demand which is sanctioned by the electricity authorities at the time of application for sanction of load. e.g. 1000 KVA.

TARGET DEMAND : It is the Maximum Demand value which we do not want to exceed. If there is no power cut, Target Demand is equal to Maximum Demand. If there is a 25% power cut then Target Demand will be 750 KVA if Maximum Demand is 1000KVA.

PRESENT DEMAND : It is zero at the beginning and increases as the load increases within the time interval of the demand period (=30 minutes). At the end of this period it returns to zero.

DEMAND FORECAST : According to the variation in the connected load this display will indicate the Maximum Demand which will be reached at the end of demand period (=30 Minutes). This will allow the user to plan the load pattern in accordance with the demand forecast, so as to avoid exceeding the Target Demand.

USEABLE REMAINING DEMAND : According to the Current Maximum Demand (connected load) the Demand Controller will calculate the Usable Demand which can be used by the consumer in the remaining demand period (=30minutes - time elapsed) such that the Maximum Demand is within the Target Demand Value. e.g. if the target demand is set at 750 KVA and the demand period =30 minutes, then at the beginning the useable demand = 750 KVA & the time display = 30 minutes. If the load is 1200 KVA at the beginning (more than the Maximum Demand and Target Demand), then the usable demand shall get reduced from 750 KVA, in the remaining time. 10 Minutes later, if the load is not changed, if the useable demand displays 600 KVA, and the remaining time displays 20 minutes, it means that the useable demand in the next 20 minutes left is 600 KVA. If the current load is not reduced from 1200 KVA to 600 KVA, then there is a risk of exceeding the target Demand 20 minutes later. Therefore current load must be reduced so as to reduce the KVA.
On the contrary if the load is less than 750 KVA in the beginning, then the usable remaining demand shall increase. If the useable demand displays 1000 KVA and the remaining time displays 10 minutes and the current load is 600 KVA, it means that 400 KVA more load can be connected for the remaining 10 minutes. The user can self arrange or adjust the load in accordance with the above explanation, so that the user does not exceed the Target Demand.

MICROPROCESSOR TRMS MAXIMUM DEMAND CONTROLLER



Click on image to Enlarge

 
  Back

Measuring Instruments

Power Clamp Meters

Thermo Hygrometers

Earth Resistance Testers Insulation Resistance Testers
Digital Multi Meters Power Meters Thermo Anemometers Earth Clamp Meters Milli Ohm Meter
Digital Clamp Meters Maximum Demand Controllers Tachometer / Stroboscopes ELCB Testers Power Supplies
Laboratory Instruments Harmonics Analysis Sound Level Meters Infrared Thermometer Oscilloscopes

Leackage Testers

Automatic Power Factor Regulator

Transmitters

Gas Analysers Calibrator
Transducers Energy Analysers Programmable Panel Meter Phasing Sticks Currency Counting Machines
Lux meters Vehicle Tracking System
Signal Transmeters L-C-R-Meters